products

OPGW Typical Designs of Central Stainless Steel Loose Tube

Details

Cable Structure:

OPGW Typical Designs of Central Stainless Steel Loose Tube

Fiber Type:

Fiber Type: G652D; G655C; 657A1; 50/125; 62.5/125; OM3; OM4 As Options

 

Applications:

●  Replacement of existing ground wires and reconstruction of old lines.

●  Applicable to low-grade lines, such as GJ50/70/90 and etc.

 

Main Features:

●  Small cable diameter, light weight, low additional load to the tower;

●  The steel tube locates at the center of the cable, no second mechanical fatigue damage.

●  Low resistance to side pressure, torsion and tensile (single layer).

 

Standard:

ITU-TG.652

Characteristics of a single mode optical fiber.

ITU-TG.655

Characteristics of a non-zero dispersion -shifted single mode fibers optical.

EIA/TIA598 B

Col code of fiber optic cables.

IEC 60794-4-10

Aerial optical cables along electrical power lines-family specification for OPGW.

IEC 60794-1-2

Optical fiber cables -part test procedures.

IEEE1138-2009

IEEE Standard for testing and performance for optical ground wire for use on electric utility power lines.

IEC 61232

Aluminum -Clad steel wire for electrical purposes.

IEC60104

Aluminum magnesium silicon alloy wire for overhead line conductors.

IEC 61089

Round wire concentric lay overhead electrical stranded conductors.

 

Technical Parameter:

Typical design for Single Layer:

Specification

Fiber Count

Diameter (mm)

Weight (kg/km)

RTS (KN)

Short Circuit (KA2s)

   

OPGW-32(40.6;4.7)

12

7.8

243

40.6

4.7

OPGW-42(54.0;8.4)

24

9

313

54

8.4

OPGW-42(43.5;10.6)

24

9

284

43.5

10.6

OPGW-54(55.9;17.5)

36

10.2

394

67.8

13.9

OPGW-57(64.5;25.3)

24

10.7

404

68.4

25.3

OPGW-61(73.7;175)

48

10.8

438

73.7

17.5

OPGW-61(55.1;24.5)

48

10.8

358

55.1

24.5

OPGW-68(80.8;21.7)

54

11.4

485

80.8

21.7

OPGW-75(54.5;41.7)

60

12

459

63

36.3

OPGW-76(54.5;41.7)

60

12

385

54.5

41.7

 

 Typical design for Double Layer:

Specification

Fiber Count

Diameter (mm)

Weight (kg/km)

RTS (KN)

Short Circuit (KA2s)

OPGW-96(121.7;42.2)

12

13

671

121.7

42.2

OPGW-127(141.0;87.9)

24

15

825

141

87.9

OPGW-127(77.8;128.0)

24

15

547

77.8

128

OPGW-145(121.0;132.2)

28

16

857

121

132.2

OPGW-163(138.2;183.6)

36

17

910

138.2

186.3

OPGW-163(99.9;213.7)

36

17

694

99.9

213.7

OPGW-183(109.7;268.7)

48

18

775

109.7

268.7

OPGW-183(118.4;261.6)

48

18

895

118.4

261.6

 

Our OPGW cables are mainly divided into: central-type stainless steel tube OPGW, stranded-type stainless steel tube OPGW, al-covered stainless steel tube OPGW, aluminum tube OPGW, lightning-resistant central stainless steel tube OPGW with compressed wires and OPPC. All the OPGW Products supplied from GL Technology meet international standards such as IEC60794 and IEEE1138 and can be manufactured according to customers' requirements.

 

Stranded Type OPGW Cable Central Type OPGW Cable
opgw-typical-designs-of-central-al-covered-stainless-steel-tube opgw-with-pbt-aluminum-tube

 

 

The advantages of GL’ OPGW Optical Ground Wire:

 

Technology: 

GL continuously develops new OPGW products like the most comprehensive and most complete OPGW accessories.

 

Manufacturer: 

Our OPGW factory with the 19 Years industrial experience,since 2023,our annual capacity is about 54,750km.Our OPGW Cable widely used in more than 80 countries and regions, Such as Ecuador, Chile, Peru, Philippines, Vietnam, Iraq, Poland, Thailand, Spain, Brazil,etc.

 

Quality: 

GL support complete, advanced test support for our OPGW Cable and hardware fittings.

 

OPGW tests shall be in accordance with applicable standards or agreements between purchaser and manufacturer.

As a general rule the tests will be performed according IEC 60794-4-10.However, if necessary tests can be done according to IEEE Std1138.

 

The Optical Fibres of OPGW cables supplied in this specification meet the requirements of ITU-T G.652.D, ITU-T G.655.

 

Type test

Type test may be waived by submitting makerʼs certificate of the similar product performed in an internationally acknowledged independent test organization or laboratory. If type test

should be performed, it will be carried out according to an extra type test procedure reached to an agreement between purchaser and manufacturer.

 

Routine test

The optical attenuation coefficient on all production cable lengths is measured according to

IEC 60793-1-CIC (Back-scattering technique, OTDR). Standard single-mode fibers are measured at 1310nm and at 1550nm. Non-zero dispersion shifted single‒mode (NZDS) fibers are

measured at 1550nm.

 

Factory test

Factory acceptance test is carried out on two samples per order in the presence of the customer or his representative. The requirements for quality characteristics are determined byrelevant standards and agreed quality plans. GL has passed the tests by authoritative institutions at China Electric Power Research Institute and Shanghai Electric Cable Research Institute.

 

Service: 

GL Provides the perfect pre-sales, sales, and post-sales service for our customers.

 

1695622451388318.jpg

For specific data sheet, please write to [email protected], whatsapp+86 18073118925 Or click here!

<<        Prev

Next       >>

[email protected] +86-18073118925